Substation Transformer Damaged Following Short Circuit
Incident Investigation
Substation Transformer Damaged Following Short Circuit
January 21, 2024
Electrical
Reference Number:
II-1665852-2024 (#43817)
Location: Aldergrove
Regulated industry sector: Electrical – Low voltage electrical system (30V to 1000V)
Incident overview
A 2000kVA unit substation transformer was damaged beyond repair after a phase to ground fault in the secondary low voltage compartment. The outdoor substation supplies power to a community center and sustained the damage after a conductor wire was installed in a way that caused it to rub against a sharp surface inside the compartment. This friction wore down the wire's insulation, exposing the wire and leading to a short circuit.