Temporary and Permanent Services for Construction Power

Information Bulletin

Information Bulletin: Temporary and Permanent Services for Construction Power

March 2, 2016

Information Bulletin
Electrical

Reference Number:

IB-EL-2016-03

Revision Number:

Rev 2



This bulletin provides guidance on the application of rules in the 2018 BC Electrical Code Regulation. The requirements of local municipal authorities having jurisdiction may vary. Installers should consult with local authorities having jurisdiction before starting work to determine their requirements.

 

A: Temporary Services and Wiring for Buildings Under Construction or Demolition

1. Scope

As outlined in rule 76-000 of the BC Electrical Code, section 76 applies to temporary wiring installations for buildings under construction or demolition. It is the nature of the installation, not the use of that installation, that determines whether the installation is temporary. Receptacles that are connected to the permanent wiring system and therefore not within the scope of section 76 are subject to other applicable rules of the BC Electrical Code. Temporary distribution panels are not considered permanent and are subject to the rules in section 76.

 

2. Receptacles

Construction sites using temporary wiring methods should be aware that this wiring is exposed to more severe duty and weather conditions than permanent installations. The use of extension cords may increase bonding conductor impedance. Additionally, site and environmental conditions may make grounding conditions unstable. These factors can result in a higher risk of electrical shock to workers. For this reason, rule 76-016 requires GFCI protection for 15 A (configuration 5-15R) and 20 A (configuration 5-20R) receptacles installed on temporary wiring installations.

 

3. Temporary Construction Operating Permit Requirements

A temporary operating permit is required for service installations that are temporary in nature and will be disconnected once the construction or demolition phase of work is completed. In many cases, the contractor installing the equipment may not be the same contractor or field safety representative who monitors ongoing safety for operation and maintenance of the equipment. The temporary operating permit authorizes installation of the equipment, and the permit holder is responsible for ensuring a field safety representative monitors the ongoing safe operation and maintenance of the equipment for the duration of its operation. The temporary operating permit must be obtained by the equipment owner. An “owner” may be the lessee as defined in the Safety Standards Act. In most cases, the site owner or builder should be the operating permit holder. The permit holder must name a field safety representative on the permit.

The temporary operating permit is valid for 12 months from date of issue. This permit is not renewable. A new, temporary construction operating permit must be obtained after 12 months if the temporary service is still required. To complete the temporary construction operating permit, the temporary construction service must be disconnected from the electrical supply before submitting a request for a Final – “All Work is Complete” inspection request.

 

4. Temporary Construction Services (Pole Mount 200 Amps or Less)

Temporary construction service installations will be accepted if they have been constructed in accordance with attached diagrams 1-2 and have satisfied the following requirements.

  1. Be protected from the weather and mechanical damage by location or by installing the equipment within an enclosure that has been made weather proof, or by using a Type 3R weatherproof enclosure, and
  2. The equipment must be capable of being locked, and
  3. All panel covers must be installed while the equipment was energized, and
  4. Receptacles supplying temporary power for construction purposes must comply with the requirements of rule 76-016, and
  5. Branch circuits must comply with the requirements of rule 76-012.
 

DIAGRAM 1

 
  • Min. Class 6 treated pole or treated 6”X 6” post (Overhead Line Guideline B-E3 090312 1)(CSA C22.3 No. 1-15)
  • Min. overhead clearance (6-112)
  • Min. pole setting depth (Overhead Line Guideline B-E3 090312 1) (CSA C22.3 No. 1-15)
  • Guy assembly requirement (Overhead Line Guideline B-E3 090312 1) (CSA C22.3 No. 1-15)
  • Supply attachment (6-112)
  • Weather proof, sealed, hinged, lockable ¾” (21mm) treated plywood enclosure: (76-006)
  • Branch circuits (76-012)
  • GFCI protection (76-016)
  • Receptacles (76-01626-708)
  • Grounding + bonding (76-004)
 

DIAGRAM 2

 
  • Min. Class 6 treated pole or treated 6”X 6” post (Overhead Line Guideline B-E3 090312 1) (CSA C22.3 No. 1-15)
  • Min. overhead clearance (6-112)
  • Min. pole depth setting (Overhead Line Guideline B-E3 090312 1) (CSA C22.3 No. 1-15)
  • Guy assembly requirement (Overhead Line Guideline B-E3 090312 1) (CSA C22.3 No. 1-15)
  • Supply attachment: (6-112)
  • Type 3R lockable enclosure: (2-400, 76-006)
  • Branch circuits: (76-012)
  • GFCI protection: (76-016)
  • Receptacles: (76-016)
  • Grounding + bonding: (76-004)
 

B: Permanent Services and Wiring for Buildings Under Construction

 

1. Electrical service equipment such as panel boards and circuit breakers installed during construction to provide temporary power must be installed to ensure the electrical equipment is not exposed to moisture or damage during the construction phase.

2. Permanently installed receptacles do not require GFCI protection even though they may be energized for use during construction. All receptacles in outdoor locations must be weather protected as required in rule 26-708. Outdoor receptacles in residential occupancies must be GFCI protected (Rule 26-722).

Permanent construction service installations will be accepted if they are constructed in accordance with attached diagrams 3 - 8 and satisfy the following requirements:

  1. Be protected from the weather and mechanical damage by location, by installing the equipment within a weatherproof enclosure, or by using a Type 3R enclosure, and
  2. The electrical service equipment must be capable of being locked, if the building is not to the lock-up stage (i.e. lockable windows and doors installed),and
  3. All panel covers must be installed while the equipment is energized, and
  4. Receptacles and branch circuits supplying temporary power for construction purposes must comply with the requirements of section 76; and
  5. Receptacles and branch circuits that form part of the permanent wiring, but are used for the construction phase must comply with the general sections of the code, and
  6. Receptacles exposed to weather must comply with rule 26-708.

DIAGRAM 3

 
  • Permanent service equipment installed (6-206, 6-208)
  • Hinged, lockable door for distribution equipment is required (2-200, 6-206)
  • Alternatively, a lockable panel cover is permitted (2-024)
  • Permanently installed branch circuits + receptacles (Section 26)
  • Temporary branch circuits + receptacles (76-012, 76-016
  • Grounding + bonding (Section 10)
 

DIAGRAM 4

 

Enclosed building (not at lock-up stage) with roofing material not installed:

  • Permanent service equipment installed (6-206, 6-208)
  • Weatherproof enclosure with sealed roof, lockable and hinged door (2-200, 2-400)
  • 6ml poly may be acceptable for roof membrane if adequately secured and sealed (2-112)
  • Permanently installed branch circuits + receptacles (Section 26)
  • Temporary branch circuits + receptacles (76-012, 76-016)
  • Grounding + bonding: (Section 10)
  • Receptacles exposed to weather (26-708)
 

DIAGRAM 5

 

Open structure exposed to weather (front view):

  • Permanent service equipment installed: (6-206, 6-208)
  • Weather proof panel enclosure complete with sealed roof, 21mm plywood, lockable and hinged door: (2-200, 2-400)
  • Exterior sheathing provided behind service equipment (2-200)
  • Temporary branch circuits + receptacles (76-012, 76-016)
  • Receptacles exposed to weather (26-708)
  • Grounding + bonding (Section 10)
 

DIAGRAM 6

 

Open structure exposed to weather (side view):

  • Permanent service equipment installed (6-206, 6-208)
  • Weather proof panel enclosure complete with sealed roof 21mm plywood, lockable and hinged door (2-200, 2-400)
  • Exterior sheathing provided behind service equipment (2-200)
  • Temporary branch circuits + receptacles (76-012, 76-016)
  • Receptacles exposed to weather (26-708)
  • Grounding + bonding (Section 10)

NOTE: Enclosure roof overhang to extend forward sufficiently to protect service equipment (when door open) from 45◦ driving rain.  

 

DIAGRAM 7

 

Permanent service pole and meter base – temporary distribution panel:

  • Min. Class 6 treated pole (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Min. overhead clearance (6-112)
  • Min. pole depth setting (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Guy assembly requirement (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Supply attachment, weather head (6-112, 6-116)
  • Type 3R lockable enclosure (2-400, 76-006)
  • Branch circuits (76-012)
  • Receptacles (76-016)
  • Receptacles exposed (26-708)
  • Grounding + bonding (Section 10)
 

DIAGRAM 8

 

Permanent service pole and combination meter base / main service breaker – temporary distribution panel:

  • Min. Class 6 treated pole (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Min. overhead clearance (6-112)
  • Min. pole depth setting (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Guy assembly requirement (Overhead Line Guideline) (CSA C22.3 No. 1-15)
  • Supply attachment, weather head (6-112, 6-116)
  • Type 3R lockable enclosure (2-400, 76-006)
  • Branch circuits (76-012)
  • Receptacles (76-016)
  • Receptacles exposed (26-708)
  • Grounding + bonding (Section 10)


Provincial Safety Manager

References:

Safety Standards Act

Electrical Safety Regulation

Safety Standards General Regulation